1.Transferring the project
A project can be transferred via the following ways:
- Via network
- Via USB flash drive
2.Transfer mode
A project transfer can be carried out in the following modes:
- Transfer images+data+voice messages
- Transfer data (not available when using a USB flash drive)
- Restart only (not available when using a USB memory device)
Note
Prior to the shutdown of the HS/FS, saving of the data to retentive memory is triggered. After shutdown the data is read out from there again.
The following is transferred:
- The entire project data
- All graphic files (Designs, Symbols, Visualisation, etc.) and settings
- All directories and files located in “
[EXP]\hsupload
” if they are selected for transfer. (See Project settings -> Interface)
[EXP]
: Path to the HS/FS Expert directory. - The files required for certificate management.
- All QuadConfig data
This mode must be used under the following circumstances:
- Before the first data transfer or before calling the user interface for the first time
- After changing graphics files
- After creating new symbols and optical modules
- After assigning other/new designs
- After changes in the QuadConfig
- After changing/adding/deleting files in “
[EXP]\hsupload
” or one of its sub-directories.
[EXP]
: Path for the HS/FS Expert directory.
Only the project data are transferred. This mode must be used after each change in the project.
Important
This mode is not available when using a USB flash drive!
This option triggers restarting of the HS/FS. No transfer of the project data takes place. The retentive data is backed up first.
Important
This mode is not available when using a USB flash drive!
When this option is activated, the data is not written to the retentive memory before shutdown of the HS/FS. Instead, the retentive memory is deleted!
Important
Please note that when the retentive memory is deleted, all configuration data entered by the user in the QuadClient, e.g. a user password which differs from the one defined in the QCConfig, the administrator password or plug-in configurations are also deleted!
When this action is activated, all the certificates on the HS/FS are deleted and created again in accordance with the procedure described here.
If a KNX keyring file was previously uploaded to the HS/FS, it can be deleted by setting this option.